  • Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
  • Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
  • Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
  • Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
  • Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
  • Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
Find Similar Products
  • Overview
  • Product Description
  • Products Show
  • Our Company
  • Production Line
  • Filed Test&Service
  • Packing & Delivery
  • Our Certifications
  • FAQ
Overview

Basic Info.

Model NO.
RBX-H
Load Way
Electronic Load
Display
Digital
Control
Computer Control
Weight
0-100Kg
Power Source
AC220V
Brand
Huayi
Service Condition
0c~40c
Delivery Time
7days
Feature
High Accuracy
Product Name
Sfra Tester
Function
Transformer Test
Package
Wooden
Power
Electronic
Customized Support
Oemodmobm, Software Reengineering
Certificate
ISO9001
Transport Package
Plywood
Trademark
HUAYI
Origin
Hubei, China
Production Capacity
100PCS/Month

Product Description

Product Description

Introduction

Sweep Frequency Response Analysis Tester Internal Fault FRA To Test Transformer  
 
 
RBX-H tester based on the measurement of the windings characteristic parameters inside the transformer, the tester using the world's developed countries sound internal fault frequency response analysis (FRA) method, able to make an accurate internal transformer fault judgment. After the completion of the design and manufacture transformers, coils and its internal structure to be finalized, therefore a
transformer coil winding, if the voltage level, method of winding are the same, each coil corresponding parameters (Ci, Li) is determined. Thus the frequency domain response characteristics of each coil also will determine, among the corresponding three-phase coil has a comparable frequency spectrum.
It occurs inter-turn, phase short circuit during the test or collision during transport, causing the coil relative displacement,
and during operation under short circuit and fault conditions due to the tension caused by the electromagnetic, coil is deformed,
it will make the distribution parameters of the transformer winding changes. Thus,influent and change the existing frequency domain transformer frequency response feature, that frequency response amplitude changes occur and resonance frequency shift, etc.
RBX-H applies to the internal structure of fault detection 63kV ~ 500kV power transformers.
FRA quantization process transformer internal winding parameters response changes in the different frequency domain, according to the value of the change magnitude, frequency response magnitude change, regional and response trends, to judge the transformer internal winding degree of change, in turn, can determine whether the transformer has been severely damaged, need to overhaul measurement.
For the running transformer, regardless of whether there is a saved frequency domain feature picture in the past, by comparison the difference between fingerprints of fault transformer coil can also judge the degree of fault. Of course, if you save a set of transformer winding original characteristic graph easier for the operation of transformers, maintenance and inspection after the accident analysis and provide a strong basis more accurate. FRA from the laptop and chip microprocessor precision measurement systems, compact, easy to operate, with comprehensive test analysis function
Technology Parameters
Linear scan distribution
Scan measurement range(1kHz)-(2MHz)2000scan frequency point, resolution 1kHz
Sectional scan measurement distribution
Scan measurement range(0.5kHz)-(1MHz)2000 scan frequency point (0.5kHz)-(10kHz)resolution 0.02kHz (10kHz)-(100kHz)resolution
0.2kHz (100kHz)-(500kHz)resolution 1kHz (500kHz)-(1000kHz)resolution 1kHz
Amplitude measurement range
(-100dB)-(+20dB)
Amplitude measurement accuracy
0.1dB
Scan frequency accuracy
less than 0.01%
Signal input impedance
1MΩ
Signal output impedance
50Ω
Co-phase repetitive rate
99.50%
Instrument dimension
300×340×120mm3
Case dimension
310×400×330mm3
Weight
10Kg
Features 
1. Use high-speed, high integration microprocessor to sample and control.
2. Use USB to connect the notebook PC and device.
3. Communication wireless Bluetooth interface between the laptop and instruments.
4. Hardware cassette mechanism adopts DDS (from America), can correctly detect the breakdown distortion, swell, shift, tilt,
inter-turn short circuit deformation and contacting short circuit inter-phase.
5. High-speed, dual channel, 16 bit A/D sampling (the wave from curve will change obviously if change the tapping switch
during the field tests.).
6. The software can adjust the output signal range, the maximum amplitude peak±10V.
7. The computer automatically generating the test results to be Word document.
8. Use precision, high stability components, the same phase repeat test, measurement repetition rate >99.5%.
9. Finished circuit boards, surface specially treatment with anti-water pollution and harmful gases.
10. The device with two measurement system: linear scan and sectional scan.
11. Amplitude-frequency characteristic comply the national technical specifications.
12. Test data automatic analysis system, horizontal compare the similarity of A,B ,C, the results as below:

* conformance is very good
* conformance is good
* conformance is bad
* conformance is very bad

Vertical compare A-AB-BC-C, obtain the original data to compare the winding deformation with the test data in the same phase,
the results as below:
* normal
* slight deformation
* moderate deformation
* serious deformation 13. Automatically generating Word documentconvenient for customers to save and print.

Accessory

 
Serial Number
Name
Amount
1
Packing case (Aluminum alloy 310mm ×400 mm ×330mm)
one
2
Mainframe (America DDS Latest frequency sweeping technology)
one
3
Bluetooth
one
4
Test cable (High frequency coaxial cable 50/15m)
one
5
Test line and clip (one orange, one green and one blue line, 20m;
one yellow clip, one green clip)
two
6
USB Communication line (3m)
one
7
Power line (international)
one
8
Ground lead (5m copper wire)
two
9
Software disc (CD format)
one
10
Fuse (0.5A)
three
11
Specification
one
12
Inspection Report
one
13
Certification
one
Products Show
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
Our Company
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
About HUAYI
Wuhan HUAYI Electric was founded in 2005, located in Wuhan City, China. We are a professional manufacturer of electric testing equipment with over 15 years industry experience, engaged in high voltage tester with high performance, good quality, customized specification and easy operation. ISO qualified factory, strong R&D team and after-sales engineers make us gain good feedback from wide customers. HUAYI is committed to preventative, maintenance, troubleshooting and commissioning all the time. Our products are involved inAC/DC Hipot tester,series resonant test systemtransformer tester, relay testercircuit breaker/switch testeroil/SF6 tester,cable testerand other electric instruments, widely adapted to electric power, water conservation, oil, railway, mine, chemical. 
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer

 

 
Production Line
We are professional manufacturer in China, have own production line and R&D team, providing best price and quality. 
 
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
Filed Test&Service
 
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
 
Packing & Delivery
 
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
 
 
 
Our Certifications
Sweep Frequency Response Analysis Tester Internal Fault Fra to Test Transformer
FAQ

1. How can I choose the suitable one?
Dear customer, please tell us your detailed requirements by mail or online, we will recommend the suitable one as your request.

2.What is the mini order quantity?
MOQ: generally 1 unit/piece/set
3. How can I pay?
Dear customer, we accept many payment term, such as T/T, Western Union...

4.Is will be broken during transport?
Dear customer, please do not worry, we do standard export package.

5.What should I do if I do not know how to use?
Dear customer, please do not worry, manual user will be sent together, you can also contact us with more technological support.

 