Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 Year |
Still deciding? Get samples of US$ 2500/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Dielectric insulation test can effectively find the insulation of electrical equipment as a whole moisture deterioration deterioration, as well as local defects, etc., in the manufacture of electricians, electrical equipment installation, handover and preventive testing are widely used; power plants, substations and other field automatic measurement of all kinds of high-voltage power equipment dielectric loss tangent value and capacitance of high-precision instruments
Pilot frequency dielectric loss tester is a high-precision testing instrument for testing dielectric loss tangent value and capacitance of various high-voltage power equipment in the field or laboratory of power plant, substation, etc. The instrument is an integrated structure with a built-in bridge for dielectric loss testing. The instrument is an integrated structure with built-in dielectric loss test bridge, variable frequency regulator power supply, step-up transformer and SF6 high stability standard capacitor. The test high voltage source is generated by the inverter inside the instrument and used for the test of the test specimen after being boosted by the transformer. The frequency can be changed to 50Hz, 47.5Hz\52.5Hz, 45Hz\55Hz, 60Hz, 57.5Hz\62.5Hz, 55Hz\65Hz, adopting the digital trap technology, avoiding the interference of the industrial frequency electric field on the test, and fundamentally solving the problem of accurate measurement under the interference of the strong electric field. At the same time, it is suitable for the occasion of testing with generator power supply after all power failure. The instrument is equipped with insulating oil cup and temperature control device to test the dielectric loss of insulating oil.
1 | Use conditions | -15ºC∽40ºC | RH<80% | |||||
2 | Anti-interference | Frequency conversion | ||||||
3 | Power | AC 220V±10% | Allowable generator | |||||
4 | High output | 0.5KV∽12KV | Every 0.1kV | |||||
Precision | 2% | |||||||
Maximum current | 200mA | |||||||
Capacity | 2000VA | |||||||
5 | Self-excited power | AC 0V∽50V/15A | 50HZ 60HZ
45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic double frequency |
|||||
6 | Resolving power | tgδ: 0.001% | Cx: 0.001pF | |||||
7 | Precision | △tgδ:±(Reading*1.0%+0.040%) | ||||||
△C x :±(Reading*1.0%+1.00PF) | ||||||||
8 | measuring range | tgδ | Unlimited | |||||
C x | 15pF < Cx < 300nF | |||||||
10KV | Cx < 60 nF | |||||||
5KV | Cx < 150 nF | |||||||
1KV | Cx < 300 nF | |||||||
CVT test | Cx < 300 nF | |||||||
9 | LCR range | L>20H(2kV) | R>10KΩ(2kV) | |||||
LCR Precision | 0.1% | Angular resolution | 0.01 | |||||
10 | CVT range | 10∽10000 | ||||||
accuracy | 0.1% | |||||||
Resolving power | 0.01 | |||||||
11 | Exterior dimension | 350(L)×270(W)×270(H) | ||||||
11 | Memory size | The 200 group supports U disk data storage | ||||||
12 | Weight | 28 Kg |
JS-8000 | ||
UST | √ | |
GST | √ | |
CVT Direct excitation | √ | |
C1/C2 test at the same time | √ | |
External connection standard | √ | |
External connection HV | √ | |
CVT Ratio test | √ | |
UST/GST test simultaneously | √ | |
LCR automatic test | √ | |
Multichannel test | ||
Insulation resistance test | ||
USB control | √ | |
U Disk storage | √ |
If you need insulation resistance test,pls chose mold JS-9000.
If you need insulation resistance tester and multichannel test,pls chose mold JS-9000R
HY has been in the market more than 19 years from 2005.Specified on all kinds of HV electrical testing equipment.Like transformer tester,ac dc hipot tester,hv hipot tester,relay protection tester,circuit breaker analyzer,contact resistance tester,insulation oil.gas analyzer ect.We are real factory to produce these hv testing equipment and electrical solution ect.
If you have any hv testing equipment or technical support needed,welcome to contact me: Sales director